This page covers replacing a drive (participating in the vSAN) due to defect or end of lifespan. Expedient replacement of problem drives is crucial to maintaining vSAN data protection.
The Verge interface will provide warnings or alerts to indicate when there is a problem with a physical drive. When a drive has a warning or error status, an indicator will "bubble up" to the System dashboard Page (To access the System dashboard: from the main dashboard, select System on the left menu.)
Click anywhere within the drive count box to access the full list of drives.
Double-click a drive with an error/warning to view its dashboard that displays more detail.
It is highly recommended to configure on-demand and scheduled subscriptions (with target type=System Dashboard) to ensure timely awareness of drive issues. Go here for information on setting up subscriptions.
If LED Status indicates Off, click Turn on LED on the left menu.
If LED Status field indicates Unsupported, click Locate LED on the left menu.
The Diagnostics window will appear with settings pre-filled.
Click Send -> to activate the drive LED .
CAUTION: Before initiating a drive repair operation, verify:
1. All nodes are operational (none are powered off or in maintenance mode);
2. Other drive repairs are not in process on a different node for the same storage tier (Drive repairs running on the same physical node pose no problem.);
3. The correct physical drive is confidently identified before removal (See directions above.)
From the node dashboard, click Drives.
Click to select the particular drive (Selected drive shows a check mark on the left.)
Click Close/Take Offline on the left menu.
When the drive status appears as Offline: physically remove the drive, being extremely careful to remove the correct drive.
Verify the UI reflects the drive is missing to verify that the proper drive was removed.
Insert the replacement drive.
Wait for the drive to be detected; the dashboard will show the new drive as Offline.
Click Format on the left menu.
Wait until the dashboard no longer indicates the disk is formatting.
Click Initialize on the left menu.
After the vSAN has completed a full walk, the repair process will begin, and the drive status will change to "Repairing"; at this point the drive dashboard will indicate an Estimated Repair Completion date and time.
DURING THE REPAIR PROCESS:
Do NOT reset or power off any nodes until the drive shows a status of "Online"; it is **important that all other nodes remain fully operational during the repair process.
Additional drive replace/repair operations should NOT be initiated until this repair operation has fully completed unless the additional drive resides: within the same node - OR - on another storage tier.